    Have a question (probably stupid, sorry guys).

    I’m not great or very experienced with N2 networks.

    JCI Facilities Explorer system.

    I have an N4 local Jace in a school pushing to an N4 server.

    School starts Monday and I have 2 dead FX07 controllers hung off of an N2 bus. Replacing them with PCG 2611 controllers.

    What’s the discovery process to bring them in to the local via the N2 network?

    I do have one unit that’s been done already so I have a wiring template and program I can pull. Just need to pull them into the N2 network. Pushing to the server out of the local is easy enough afterwards.

    “I haven’t failed. I’ve just found 10,000 ways that won’t work.” – Thomas Edison

    “It’s not whether you get knocked down, it’s whether you get up.” – Vince Lombardi

    “In this house we obey the laws of thermodynamics” – Homer Simpson

    Local 486 Instructor & Service Technician







  • Start with this to discover the new PCGs. https://docs.johnsoncontrols.com/bas…ice-Components

    You’ll also need a resource file to bring in the points. In your case, I think you’ll need the CAF for each controller. I’m not an expert on N2, but hopefully this gets you pointed in the right direction.
    I also like your Homer Simpson quote. Lisa’s perpetual motion machine that he considered a “joke.”







  • N4/AX will not discover N2 devices points, older UNT/FX, etc and newer PCG/V configured for N2. Need to use the prn file to create your points list in N4/AX for N2 devices. In CCT/PCT you can create a PRN for PCG/V controllers if configured for N2, it is under the same tab where you map out the N2 points …..